[{"data":1,"prerenderedAt":1959},["ShallowReactive",2],{"blog-post-nl-badkamer-kabels-arei-zones":3,"blog-alternates-bathroom-cables-arei-zones":450},{"id":4,"title":5,"articleId":6,"body":7,"category":420,"date":421,"description":422,"extension":423,"lastUpdated":421,"locale":424,"meta":425,"navigation":426,"path":427,"publishDate":421,"readTime":428,"refreshInterval":429,"seo":430,"slug":431,"stem":432,"tags":433,"__hash__":449},"blog\u002Fblog\u002Fbathroom-cables-arei-zones.nl.md","Welke kabels mag ik gebruiken in de badkamer? (AREI-zones)","bathroom-cables-arei-zones",{"type":8,"value":9,"toc":406},"minimark",[10,15,28,32,39,104,117,120,124,239,244,276,280,350,354,361,374,378,381,385,400],[11,12,14],"h2",{"id":13},"xvb-is-altijd-toegelaten-vob-alleen-onder-voorwaarden","XVB is altijd toegelaten — VOB alleen onder voorwaarden",[16,17,18,19,23,24,27],"p",{},"Bij de elektrische installatie in de badkamer gelden in België bijzondere voorschriften. De belangrijkste vuistregel: ",[20,21,22],"strong",{},"XVB-kabel"," (mantelleiding) is in alle badkamerzones toegelaten. ",[20,25,26],{},"VOB-draad in buis"," (Preflex) is aan beperkingen onderworpen — vooral in holle wanden.",[11,29,31],{"id":30},"de-arei-badkamerzones","De AREI-badkamerzones",[16,33,34,35,38],{},"Het AREI definieert ",[20,36,37],{},"drie zones"," rond bad en douche: Zone 0, Zone 1, Zone 2 (alleen bij badkuipen) en het gebied buiten de zones (Art. 7.1.3.2).",[40,41,42,58],"table",{},[43,44,45],"thead",{},[46,47,48,52,55],"tr",{},[49,50,51],"th",{},"Zone",[49,53,54],{},"Gebied",[49,56,57],{},"Toegelaten installatie",[59,60,61,75,88],"tbody",{},[46,62,63,69,72],{},[64,65,66],"td",{},[20,67,68],{},"Zone 0",[64,70,71],{},"Binnenkant van het bad\u002Fde douche",[64,73,74],{},"Alleen ZLVS ≤ 12V, IPX7",[46,76,77,82,85],{},[64,78,79],{},[20,80,81],{},"Zone 1",[64,83,84],{},"Loodrecht boven zone 0, tot 2,25 m hoogte",[64,86,87],{},"Vast aangesloten toestellen ≥ IPX4; ZLVS-stopcontacten en ZLVS-schakelaars toegelaten (Art. 7.1.5.2c Nr. 2 en 4)",[46,89,90,95,101],{},[64,91,92],{},[20,93,94],{},"Zone 2",[64,96,97,98],{},"60 cm rond zone 1 — ",[20,99,100],{},"alleen bij badkuipen",[64,102,103],{},"Stopcontacten met 30mA differentieel toegelaten, toestellen ≥ IPX4",[105,106,107],"blockquote",{},[16,108,109,112,113,116],{},[20,110,111],{},"Belangrijk:"," Zone 2 is voor douches ",[20,114,115],{},"niet gedefinieerd"," (Art. 7.1.3.2 Nr. 3b). Bij douches volgt op zone 1 direct het gebied buiten de zones.",[16,118,119],{},"Buiten deze zones gelden de normale installatieregels.",[11,121,123],{"id":122},"kabeltypes-en-hun-toelaatbaarheid","Kabeltypes en hun toelaatbaarheid",[40,125,126,145],{},[43,127,128],{},[46,129,130,133,136,138,140,142],{},[49,131,132],{},"Kabeltype",[49,134,135],{},"CPR-klasse",[49,137,68],{},[49,139,81],{},[49,141,94],{},[49,143,144],{},"Buiten zones",[59,146,147,167,185,203,222],{},[46,148,149,154,157,160,163,165],{},[64,150,151],{},[20,152,153],{},"XVB 3G2,5",[64,155,156],{},"Cca",[64,158,159],{},"Nee",[64,161,162],{},"Ja",[64,164,162],{},[64,166,162],{},[46,168,169,174,176,178,181,183],{},[64,170,171],{},[20,172,173],{},"XVB 3G1,5",[64,175,156],{},[64,177,159],{},[64,179,180],{},"Ja (verlichting)",[64,182,162],{},[64,184,162],{},[46,186,187,192,195,197,199,201],{},[64,188,189],{},[20,190,191],{},"VOB in grijze Preflex",[64,193,194],{},"—",[64,196,159],{},[64,198,162],{},[64,200,162],{},[64,202,162],{},[46,204,205,210,212,214,217,220],{},[64,206,207],{},[20,208,209],{},"VOB in groene Preflex",[64,211,194],{},[64,213,159],{},[64,215,216],{},"Nee (holle wand)",[64,218,219],{},"Beperkt",[64,221,162],{},[46,223,224,229,231,233,235,237],{},[64,225,226],{},[20,227,228],{},"H07Z1-U (halogeenvrij)",[64,230,156],{},[64,232,159],{},[64,234,162],{},[64,236,162],{},[64,238,162],{},[240,241,243],"h3",{"id":242},"belangrijke-opmerkingen-bij-de-kabeltypes","Belangrijke opmerkingen bij de kabeltypes",[245,246,247,254,264,270],"ul",{},[248,249,250,253],"li",{},[20,251,252],{},"XVB"," (mantelleiding): Altijd de veilige keuze. Geschikt voor inbouw, opbouw en in kabelgoten.",[248,255,256,259,260,263],{},[20,257,258],{},"Grijze Preflex"," (standaard buis met voorgetrokken VOB): Toegelaten in massieve wanden. ",[20,261,262],{},"Niet"," in holle wanden of verlaagde plafonds.",[248,265,266,269],{},[20,267,268],{},"Preflex Safe (groen)",": In massieve wanden is Preflex Safe (Cca) ook in zone 1 toegelaten. De beperking geldt voor holle wanden (droogbouw), niet voor de zone zelf.",[248,271,272,275],{},[20,273,274],{},"H07Z1-U",": Halogeenvrije draad, vooral aanbevolen voor gevoelige zones. Let op: H07Z1-U als enkeldraad heeft geen inherente CPR-klasse Cca — de klasse verwijst naar het kabelsysteem (draad + buis). H07Z1-U in Preflex Safe bereikt Cca.",[11,277,279],{"id":278},"doorsnede-tabel","Doorsnede-tabel",[40,281,282,295],{},[43,283,284],{},[46,285,286,289,292],{},[49,287,288],{},"Gebruik",[49,290,291],{},"Min. doorsnede",[49,293,294],{},"Automaat",[59,296,297,308,319,329,339],{},[46,298,299,302,305],{},[64,300,301],{},"Verlichting",[64,303,304],{},"1,5 mm²",[64,306,307],{},"10A of 16A",[46,309,310,313,316],{},[64,311,312],{},"Stopcontacten",[64,314,315],{},"2,5 mm²",[64,317,318],{},"16A of 20A",[46,320,321,324,326],{},[64,322,323],{},"Wasmachine \u002F droogkast",[64,325,315],{},[64,327,328],{},"16A (eigen kring)",[46,330,331,334,336],{},[64,332,333],{},"Elektrische boiler (onder aanrecht, ≤ 2 kW)",[64,335,315],{},[64,337,338],{},"16A",[46,340,341,344,347],{},[64,342,343],{},"Elektrische doorstromer (18–27 kW)",[64,345,346],{},"6 mm² (32A) of 10 mm² (40A, driefasig)",[64,348,349],{},"32A of 40A",[11,351,353],{"id":352},"_30ma-differentieelbescherming-is-verplicht","30mA differentieelbescherming is verplicht",[16,355,356,357,360],{},"Volgens AREI Art. 7.1.4.3 moeten ",[20,358,359],{},"alle kringen in de badkamer"," beschermd zijn door een 30mA differentieel — zonder uitzondering. Dit geldt voor verlichting, stopcontacten en vast aangesloten toestellen.",[105,362,363],{},[16,364,365,368,369,373],{},[20,366,367],{},"Let op",": Ook kringen die alleen maar ",[370,371,372],"em",{},"door"," de badkamer lopen (bijv. kabels naar de zolder) moeten aan de zone-eisen voldoen als ze binnen de beschermingszones lopen.",[11,375,377],{"id":376},"potentiaalvereffening-in-de-badkamer","Potentiaalvereffening in de badkamer",[16,379,380],{},"Belangrijk: Het AREI (Art. 7.1.4.4) vereist een bijkomende potentiaalvereffening in de badkamer — alle metalen delen (waterleidingen, radiatoren, badkuip, afvoerleidingen) moeten via een beschermingsleider onderling en met de hoofdaardingsklem verbonden worden. Ontbrekende potentiaalvereffening is een veelvoorkomende reden voor afkeuring bij de keuring.",[11,382,384],{"id":383},"gerelateerde-artikelen","Gerelateerde artikelen",[245,386,387,394],{},[248,388,389],{},[390,391,393],"a",{"href":392},"\u002Fblog\u002F30ma-aardlek-per-stopcontact","Heb ik een 30mA differentieel nodig per stopcontact?",[248,395,396],{},[390,397,399],{"href":398},"\u002Fblog\u002Felektrische-keuring","Elektrische keuring in België — wat u moet weten",[16,401,402],{},[390,403,405],{"href":404},"\u002F","Plan uw badkamerelektriciteit met PlanElec — gratis →",{"title":407,"searchDepth":408,"depth":408,"links":409},"",2,[410,411,412,416,417,418,419],{"id":13,"depth":408,"text":14},{"id":30,"depth":408,"text":31},{"id":122,"depth":408,"text":123,"children":413},[414],{"id":242,"depth":415,"text":243},3,{"id":278,"depth":408,"text":279},{"id":352,"depth":408,"text":353},{"id":376,"depth":408,"text":377},{"id":383,"depth":408,"text":384},"faq","2026-03-09","XVB is altijd toegelaten, VOB in buis alleen onder voorwaarden. Ontdek welke kabeltypes zijn toegestaan in elke AREI-zone en waar u op moet letten.","md","nl",{},true,"\u002Fblog\u002Fbathroom-cables-arei-zones.nl","4 min",12,{"title":5,"description":422},"badkamer-kabels-arei-zones","blog\u002Fbathroom-cables-arei-zones.nl",[434,435,436,437,252,438,439,440,441,442,443,444,445,446,447,448],"AREI","RGIE","badkamer","zones","VOB","Preflex","kabels","differentieel","30mA","keuring","elektrische installatie","België","eendraadschema","situatieschema","CPR","FGPbM7vnU3id6vpaedLue-WoNAfOres3urO8n7x1Ta8",[451,855,1259,1658],{"id":452,"title":453,"articleId":6,"body":454,"category":420,"date":421,"description":836,"extension":423,"lastUpdated":421,"locale":837,"meta":838,"navigation":426,"path":839,"publishDate":421,"readTime":428,"refreshInterval":429,"seo":840,"slug":841,"stem":842,"tags":843,"__hash__":854},"blog\u002Fblog\u002Fbathroom-cables-arei-zones.de.md","Welche Kabel darf ich im Badezimmer verwenden? (AREI Zonen)",{"type":8,"value":455,"toc":825},[456,460,471,475,482,540,552,555,559,669,673,701,705,772,776,783,795,799,802,806,820],[11,457,459],{"id":458},"xvb-ist-immer-erlaubt-vob-nur-eingeschränkt","XVB ist immer erlaubt — VOB nur eingeschränkt",[16,461,462,463,466,467,470],{},"Bei der Elektroinstallation im Badezimmer gelten in Belgien besondere Vorschriften. Die wichtigste Faustregel: ",[20,464,465],{},"XVB-Kabel"," (Mantelleitung) ist in allen Badezimmerzonen erlaubt. ",[20,468,469],{},"VOB-Draht in Leerrohr"," (Preflex) unterliegt Einschränkungen — insbesondere in Hohlwänden.",[11,472,474],{"id":473},"die-arei-badezimmerzonen","Die AREI-Badezimmerzonen",[16,476,477,478,481],{},"Das AREI definiert ",[20,479,480],{},"drei Bereiche"," rund um Badewanne und Dusche: Bereich 0, Bereich 1, Bereich 2 (nur bei Badewannen) und den Bereich außerhalb der Zonen (Art. 7.1.3.2).",[40,483,484,496],{},[43,485,486],{},[46,487,488,490,493],{},[49,489,51],{},[49,491,492],{},"Bereich",[49,494,495],{},"Erlaubte Installation",[59,497,498,511,524],{},[46,499,500,505,508],{},[64,501,502],{},[20,503,504],{},"Bereich 0",[64,506,507],{},"Inneres der Badewanne\u002FDusche",[64,509,510],{},"Nur SELV ≤ 12V, IPX7",[46,512,513,518,521],{},[64,514,515],{},[20,516,517],{},"Bereich 1",[64,519,520],{},"Senkrecht über Bereich 0, bis 2,25 m Höhe",[64,522,523],{},"Fest angeschlossene Geräte ≥ IPX4; SELV-Steckdosen und SELV-Schalter erlaubt (Art. 7.1.5.2c Nr. 2 und 4)",[46,525,526,531,537],{},[64,527,528],{},[20,529,530],{},"Bereich 2",[64,532,533,534],{},"60 cm um Bereich 1 herum — ",[20,535,536],{},"nur bei Badewannen",[64,538,539],{},"Steckdosen mit 30mA-FI erlaubt, Geräte ≥ IPX4",[105,541,542],{},[16,543,544,547,548,551],{},[20,545,546],{},"Wichtig:"," Bereich 2 ist für Duschen ",[20,549,550],{},"nicht festgelegt"," (Art. 7.1.3.2 Nr. 3b). Bei Duschen folgt auf Bereich 1 direkt der Bereich außerhalb der Zonen.",[16,553,554],{},"Außerhalb dieser Zonen gelten die normalen Installationsregeln.",[11,556,558],{"id":557},"kabeltypen-und-ihre-zulässigkeit","Kabeltypen und ihre Zulässigkeit",[40,560,561,580],{},[43,562,563],{},[46,564,565,568,571,573,575,577],{},[49,566,567],{},"Kabeltyp",[49,569,570],{},"CPR-Klasse",[49,572,68],{},[49,574,81],{},[49,576,94],{},[49,578,579],{},"Außerhalb",[59,581,582,599,616,633,652],{},[46,583,584,588,590,593,595,597],{},[64,585,586],{},[20,587,153],{},[64,589,156],{},[64,591,592],{},"Nein",[64,594,162],{},[64,596,162],{},[64,598,162],{},[46,600,601,605,607,609,612,614],{},[64,602,603],{},[20,604,173],{},[64,606,156],{},[64,608,592],{},[64,610,611],{},"Ja (Beleuchtung)",[64,613,162],{},[64,615,162],{},[46,617,618,623,625,627,629,631],{},[64,619,620],{},[20,621,622],{},"VOB in Preflex grau",[64,624,194],{},[64,626,592],{},[64,628,162],{},[64,630,162],{},[64,632,162],{},[46,634,635,640,642,644,647,650],{},[64,636,637],{},[20,638,639],{},"VOB in Preflex grün",[64,641,194],{},[64,643,592],{},[64,645,646],{},"Nein (Hohlwand)",[64,648,649],{},"Eingeschränkt",[64,651,162],{},[46,653,654,659,661,663,665,667],{},[64,655,656],{},[20,657,658],{},"H07Z1-U (halogenfrei)",[64,660,156],{},[64,662,592],{},[64,664,162],{},[64,666,162],{},[64,668,162],{},[240,670,672],{"id":671},"wichtige-hinweise-zu-den-kabeltypen","Wichtige Hinweise zu den Kabeltypen",[245,674,675,680,690,696],{},[248,676,677,679],{},[20,678,252],{}," (Mantelleitung): Immer die sichere Wahl. Geeignet für Unterputz, Aufputz und in Kabelkanälen.",[248,681,682,685,686,689],{},[20,683,684],{},"Preflex grau"," (normales Leerrohr mit vorgezogenem VOB): Zulässig in Massivwänden. ",[20,687,688],{},"Nicht"," in Hohlwänden\u002FZwischendecken verwenden.",[248,691,692,695],{},[20,693,694],{},"Preflex Safe (grün)",": In Massivwänden ist Preflex Safe (Cca) auch in Zone 1 zulässig. Die Einschränkung betrifft Hohlwände (droogbouw), nicht die Zone selbst.",[248,697,698,700],{},[20,699,274],{},": Halogenfreier Draht, besonders für sensible Bereiche empfohlen. Hinweis: H07Z1-U als Einzeldraht hat keine inhärente CPR-Klasse Cca — die Klasse bezieht sich auf das Kabelsystem (Draht + Rohr). H07Z1-U in Preflex Safe erreicht Cca.",[11,702,704],{"id":703},"querschnitt-tabelle","Querschnitt-Tabelle",[40,706,707,720],{},[43,708,709],{},[46,710,711,714,717],{},[49,712,713],{},"Verwendung",[49,715,716],{},"Min. Querschnitt",[49,718,719],{},"Sicherung",[59,721,722,732,742,752,761],{},[46,723,724,727,729],{},[64,725,726],{},"Beleuchtung",[64,728,304],{},[64,730,731],{},"10A oder 16A",[46,733,734,737,739],{},[64,735,736],{},"Steckdosen",[64,738,315],{},[64,740,741],{},"16A oder 20A",[46,743,744,747,749],{},[64,745,746],{},"Waschmaschine\u002FTrockner",[64,748,315],{},[64,750,751],{},"16A (eigener Stromkreis)",[46,753,754,757,759],{},[64,755,756],{},"Elektrischer Boiler (Untertisch, ≤ 2 kW)",[64,758,315],{},[64,760,338],{},[46,762,763,766,769],{},[64,764,765],{},"Elektrischer Durchlauferhitzer (18–27 kW)",[64,767,768],{},"6 mm² (32A) oder 10 mm² (40A, Dreiphasen)",[64,770,771],{},"32A oder 40A",[11,773,775],{"id":774},"_30ma-differentialschutz-ist-pflicht","30mA-Differentialschutz ist Pflicht",[16,777,778,779,782],{},"Gemäß AREI Art. 7.1.4.3 müssen ",[20,780,781],{},"alle Stromkreise im Badezimmer"," durch einen 30mA-FI-Schutzschalter gesichert sein — ohne Ausnahme. Dies gilt für Beleuchtung, Steckdosen und fest angeschlossene Geräte gleichermaßen.",[105,784,785],{},[16,786,787,790,791,794],{},[20,788,789],{},"Achtung",": Auch Stromkreise, die nur ",[370,792,793],{},"durch"," das Badezimmer verlaufen (z.B. Kabel zum Dachboden), müssen den Zonenvorgaben entsprechen, wenn sie innerhalb der Schutzzonen verlegt werden.",[11,796,798],{"id":797},"potentialausgleich-im-badezimmer","Potentialausgleich im Badezimmer",[16,800,801],{},"Wichtig: Das AREI (Art. 7.1.4.4) verlangt einen zusätzlichen Potentialausgleich im Badezimmer — alle metallischen Teile (Wasserrohre, Heizkörper, Badewanne, Abflussrohre) müssen über einen Schutzleiter miteinander und mit der Haupterdungsschiene verbunden werden. Fehlender Potentialausgleich ist ein häufiger Mängelgrund bei der Keuring.",[11,803,805],{"id":804},"verwandte-artikel","Verwandte Artikel",[245,807,808,814],{},[248,809,810],{},[390,811,813],{"href":812},"\u002Fde\u002Fblog\u002F30ma-fi-pro-steckdose","Brauche ich einen 30mA FI-Schalter für jede Steckdose?",[248,815,816],{},[390,817,819],{"href":818},"\u002Fde\u002Fblog\u002Felektrische-abnahme","Elektrische Abnahme in Belgien — was Sie wissen müssen",[16,821,822],{},[390,823,824],{"href":404},"Planen Sie Ihre Badezimmer-Elektrik mit PlanElec — kostenlos →",{"title":407,"searchDepth":408,"depth":408,"links":826},[827,828,829,832,833,834,835],{"id":458,"depth":408,"text":459},{"id":473,"depth":408,"text":474},{"id":557,"depth":408,"text":558,"children":830},[831],{"id":671,"depth":415,"text":672},{"id":703,"depth":408,"text":704},{"id":774,"depth":408,"text":775},{"id":797,"depth":408,"text":798},{"id":804,"depth":408,"text":805},"XVB ist immer erlaubt, VOB in Leerrohr nur eingeschränkt. Erfahren Sie, welche Kabeltypen in welcher AREI-Zone zulässig sind und worauf Sie achten müssen.","de",{},"\u002Fblog\u002Fbathroom-cables-arei-zones.de",{"title":453,"description":836},"badezimmer-kabel-arei-zonen","blog\u002Fbathroom-cables-arei-zones.de",[434,435,844,845,252,438,439,846,847,442,848,849,850,851,852,853,448],"Badezimmer","Zonen","Kabel","FI-Schutzschalter","Stromabnahme","Keuring","elektrische Installation","Belgien","Eindrahtschema","Situationsplan","u2AFNJg-k2r8mglgueyvhWHNcS5d15hMluMaeHzJQkE",{"id":856,"title":857,"articleId":6,"body":858,"category":420,"date":421,"description":1242,"extension":423,"lastUpdated":421,"locale":1243,"meta":1244,"navigation":426,"path":1245,"publishDate":421,"readTime":428,"refreshInterval":429,"seo":1246,"slug":6,"stem":1247,"tags":1248,"__hash__":1258},"blog\u002Fblog\u002Fbathroom-cables-arei-zones.en.md","Which Cables Can I Use in the Bathroom? (AREI Zones)",{"type":8,"value":859,"toc":1231},[860,864,875,879,886,941,953,956,960,1073,1077,1105,1109,1178,1182,1189,1201,1205,1208,1212,1226],[11,861,863],{"id":862},"xvb-is-always-allowed-vob-only-with-restrictions","XVB is always allowed — VOB only with restrictions",[16,865,866,867,870,871,874],{},"Bathroom electrical installations in Belgium are subject to special regulations. The key rule of thumb: ",[20,868,869],{},"XVB cable"," (sheathed cable) is permitted in all bathroom zones. ",[20,872,873],{},"VOB wire in conduit"," (Preflex) has restrictions — especially in hollow walls.",[11,876,878],{"id":877},"the-arei-bathroom-zones","The AREI bathroom zones",[16,880,881,882,885],{},"The AREI defines ",[20,883,884],{},"three zones"," around bathtubs and showers: Zone 0, Zone 1, Zone 2 (bathtubs only), and the area outside the zones (Art. 7.1.3.2).",[40,887,888,900],{},[43,889,890],{},[46,891,892,894,897],{},[49,893,51],{},[49,895,896],{},"Area",[49,898,899],{},"Permitted installation",[59,901,902,914,926],{},[46,903,904,908,911],{},[64,905,906],{},[20,907,68],{},[64,909,910],{},"Inside the bathtub\u002Fshower",[64,912,913],{},"SELV ≤ 12V only, IPX7",[46,915,916,920,923],{},[64,917,918],{},[20,919,81],{},[64,921,922],{},"Vertically above Zone 0, up to 2.25 m height",[64,924,925],{},"Fixed appliances ≥ IPX4; SELV sockets and SELV switches permitted (Art. 7.1.5.2c Nr. 2 and 4)",[46,927,928,932,938],{},[64,929,930],{},[20,931,94],{},[64,933,934,935],{},"60 cm around Zone 1 — ",[20,936,937],{},"bathtubs only",[64,939,940],{},"Sockets with 30mA RCD allowed, appliances ≥ IPX4",[105,942,943],{},[16,944,945,948,949,952],{},[20,946,947],{},"Important:"," Zone 2 is ",[20,950,951],{},"not defined"," for showers (Art. 7.1.3.2 Nr. 3b). For showers, Zone 1 is followed directly by the area outside the zones.",[16,954,955],{},"Outside these zones, normal installation rules apply.",[11,957,959],{"id":958},"cable-types-and-their-permissibility","Cable types and their permissibility",[40,961,962,981],{},[43,963,964],{},[46,965,966,969,972,974,976,978],{},[49,967,968],{},"Cable type",[49,970,971],{},"CPR class",[49,973,68],{},[49,975,81],{},[49,977,94],{},[49,979,980],{},"Outside zones",[59,982,983,1002,1020,1037,1056],{},[46,984,985,990,992,995,998,1000],{},[64,986,987],{},[20,988,989],{},"XVB 3G2.5",[64,991,156],{},[64,993,994],{},"No",[64,996,997],{},"Yes",[64,999,997],{},[64,1001,997],{},[46,1003,1004,1009,1011,1013,1016,1018],{},[64,1005,1006],{},[20,1007,1008],{},"XVB 3G1.5",[64,1010,156],{},[64,1012,994],{},[64,1014,1015],{},"Yes (lighting)",[64,1017,997],{},[64,1019,997],{},[46,1021,1022,1027,1029,1031,1033,1035],{},[64,1023,1024],{},[20,1025,1026],{},"VOB in grey Preflex",[64,1028,194],{},[64,1030,994],{},[64,1032,997],{},[64,1034,997],{},[64,1036,997],{},[46,1038,1039,1044,1046,1048,1051,1054],{},[64,1040,1041],{},[20,1042,1043],{},"VOB in green Preflex",[64,1045,194],{},[64,1047,994],{},[64,1049,1050],{},"No (hollow wall)",[64,1052,1053],{},"Restricted",[64,1055,997],{},[46,1057,1058,1063,1065,1067,1069,1071],{},[64,1059,1060],{},[20,1061,1062],{},"H07Z1-U (halogen-free)",[64,1064,156],{},[64,1066,994],{},[64,1068,997],{},[64,1070,997],{},[64,1072,997],{},[240,1074,1076],{"id":1075},"important-notes-on-cable-types","Important notes on cable types",[245,1078,1079,1084,1094,1100],{},[248,1080,1081,1083],{},[20,1082,252],{}," (sheathed cable): Always the safe choice. Suitable for flush mounting, surface mounting, and cable trays.",[248,1085,1086,1089,1090,1093],{},[20,1087,1088],{},"Grey Preflex"," (standard conduit with pre-pulled VOB): Permitted in solid walls. ",[20,1091,1092],{},"Not"," allowed in hollow walls or suspended ceilings.",[248,1095,1096,1099],{},[20,1097,1098],{},"Preflex Safe (green)",": In solid walls, Preflex Safe (Cca) is also permitted in Zone 1. The restriction applies to hollow walls (droogbouw), not the zone itself.",[248,1101,1102,1104],{},[20,1103,274],{},": Halogen-free wire, particularly recommended for sensitive areas. Note: H07Z1-U as a single wire does not inherently have a CPR class of Cca — the class refers to the cable system (wire + conduit). H07Z1-U in Preflex Safe achieves Cca.",[11,1106,1108],{"id":1107},"cross-section-table","Cross-section table",[40,1110,1111,1124],{},[43,1112,1113],{},[46,1114,1115,1118,1121],{},[49,1116,1117],{},"Usage",[49,1119,1120],{},"Min. cross-section",[49,1122,1123],{},"Circuit breaker",[59,1125,1126,1137,1148,1158,1167],{},[46,1127,1128,1131,1134],{},[64,1129,1130],{},"Lighting",[64,1132,1133],{},"1.5 mm²",[64,1135,1136],{},"10A or 16A",[46,1138,1139,1142,1145],{},[64,1140,1141],{},"Sockets",[64,1143,1144],{},"2.5 mm²",[64,1146,1147],{},"16A or 20A",[46,1149,1150,1153,1155],{},[64,1151,1152],{},"Washing machine \u002F dryer",[64,1154,1144],{},[64,1156,1157],{},"16A (dedicated circuit)",[46,1159,1160,1163,1165],{},[64,1161,1162],{},"Electric water heater (under-sink, ≤ 2 kW)",[64,1164,1144],{},[64,1166,338],{},[46,1168,1169,1172,1175],{},[64,1170,1171],{},"Electric instantaneous water heater (18–27 kW)",[64,1173,1174],{},"6 mm² (32A) or 10 mm² (40A, three-phase)",[64,1176,1177],{},"32A or 40A",[11,1179,1181],{"id":1180},"_30ma-differential-protection-is-mandatory","30mA differential protection is mandatory",[16,1183,1184,1185,1188],{},"According to AREI Art. 7.1.4.3, ",[20,1186,1187],{},"all circuits in the bathroom"," must be protected by a 30mA RCD — no exceptions. This applies equally to lighting, sockets, and fixed appliances.",[105,1190,1191],{},[16,1192,1193,1196,1197,1200],{},[20,1194,1195],{},"Warning",": Even circuits that merely ",[370,1198,1199],{},"pass through"," the bathroom (e.g., cables to the attic) must comply with zone requirements if they run within the protection zones.",[11,1202,1204],{"id":1203},"equipotential-bonding-in-the-bathroom","Equipotential bonding in the bathroom",[16,1206,1207],{},"Important: The AREI (Art. 7.1.4.4) requires supplementary equipotential bonding in the bathroom — all metallic parts (water pipes, radiators, bathtub, drain pipes) must be connected to each other and to the main earthing terminal via a protective conductor. Missing equipotential bonding is a common reason for inspection failure.",[11,1209,1211],{"id":1210},"related-articles","Related articles",[245,1213,1214,1220],{},[248,1215,1216],{},[390,1217,1219],{"href":1218},"\u002Fen\u002Fblog\u002F30ma-rcd-per-socket","Do I need a 30mA RCD for every socket?",[248,1221,1222],{},[390,1223,1225],{"href":1224},"\u002Fen\u002Fblog\u002Felectrical-inspection","Electrical inspection in Belgium — what you need to know",[16,1227,1228],{},[390,1229,1230],{"href":404},"Plan your bathroom electrics with PlanElec — free →",{"title":407,"searchDepth":408,"depth":408,"links":1232},[1233,1234,1235,1238,1239,1240,1241],{"id":862,"depth":408,"text":863},{"id":877,"depth":408,"text":878},{"id":958,"depth":408,"text":959,"children":1236},[1237],{"id":1075,"depth":415,"text":1076},{"id":1107,"depth":408,"text":1108},{"id":1180,"depth":408,"text":1181},{"id":1203,"depth":408,"text":1204},{"id":1210,"depth":408,"text":1211},"XVB is always permitted, VOB in conduit only with restrictions. Learn which cable types are allowed in each AREI zone and what to watch out for.","en",{},"\u002Fblog\u002Fbathroom-cables-arei-zones.en",{"title":857,"description":1242},"blog\u002Fbathroom-cables-arei-zones.en",[434,435,1249,437,252,438,439,1250,1251,442,1252,443,1253,1254,1255,446,852,1256,1257,448],"bathroom","cables","RCD","inspection","electrical installation","Belgium","single-line diagram","schéma unifilaire","situation plan","ZgbQLsxNNJRX4smfwHGocQCncIUqNvJMapcLmRmLIdU",{"id":1260,"title":1261,"articleId":6,"body":1262,"category":420,"date":421,"description":1642,"extension":423,"lastUpdated":421,"locale":1643,"meta":1644,"navigation":426,"path":1645,"publishDate":421,"readTime":428,"refreshInterval":429,"seo":1646,"slug":1647,"stem":1648,"tags":1649,"__hash__":1657},"blog\u002Fblog\u002Fbathroom-cables-arei-zones.fr.md","Quels câbles utiliser dans la salle de bain ? (Zones RGIE)",{"type":8,"value":1263,"toc":1631},[1264,1268,1279,1283,1290,1345,1357,1360,1364,1475,1479,1507,1511,1578,1582,1589,1601,1605,1608,1612,1626],[11,1265,1267],{"id":1266},"le-xvb-est-toujours-autorisé-le-vob-sous-conditions","Le XVB est toujours autorisé — le VOB sous conditions",[16,1269,1270,1271,1274,1275,1278],{},"L'installation électrique dans la salle de bain est soumise à des règles particulières en Belgique. La règle de base : le ",[20,1272,1273],{},"câble XVB"," (câble sous gaine) est autorisé dans toutes les zones de la salle de bain. Le ",[20,1276,1277],{},"fil VOB en conduit"," (Preflex) est soumis à des restrictions — notamment dans les cloisons creuses.",[11,1280,1282],{"id":1281},"les-zones-rgie-de-la-salle-de-bain","Les zones RGIE de la salle de bain",[16,1284,1285,1286,1289],{},"Le RGIE définit ",[20,1287,1288],{},"trois zones"," autour de la baignoire et de la douche : zone 0, zone 1, zone 2 (uniquement pour les baignoires) et la zone hors périmètre (art. 7.1.3.2).",[40,1291,1292,1304],{},[43,1293,1294],{},[46,1295,1296,1298,1301],{},[49,1297,51],{},[49,1299,1300],{},"Périmètre",[49,1302,1303],{},"Installation autorisée",[59,1305,1306,1318,1330],{},[46,1307,1308,1312,1315],{},[64,1309,1310],{},[20,1311,68],{},[64,1313,1314],{},"Intérieur de la baignoire\u002Fdouche",[64,1316,1317],{},"TBTS ≤ 12V uniquement, IPX7",[46,1319,1320,1324,1327],{},[64,1321,1322],{},[20,1323,81],{},[64,1325,1326],{},"Verticalement au-dessus de la zone 0, jusqu'à 2,25 m de hauteur",[64,1328,1329],{},"Appareils fixes ≥ IPX4 ; prises TBTS et interrupteurs TBTS autorisés (art. 7.1.5.2c n° 2 et 4)",[46,1331,1332,1336,1342],{},[64,1333,1334],{},[20,1335,94],{},[64,1337,1338,1339],{},"60 cm autour de la zone 1 — ",[20,1340,1341],{},"uniquement pour les baignoires",[64,1343,1344],{},"Prises avec différentiel 30mA autorisées, appareils ≥ IPX4",[105,1346,1347],{},[16,1348,1349,1352,1353,1356],{},[20,1350,1351],{},"Important :"," La zone 2 n'est ",[20,1354,1355],{},"pas définie"," pour les douches (art. 7.1.3.2 n° 3b). Pour les douches, la zone 1 est directement suivie de la zone hors périmètre.",[16,1358,1359],{},"En dehors de ces zones, les règles d'installation normales s'appliquent.",[11,1361,1363],{"id":1362},"types-de-câbles-et-leur-admissibilité","Types de câbles et leur admissibilité",[40,1365,1366,1385],{},[43,1367,1368],{},[46,1369,1370,1373,1376,1378,1380,1382],{},[49,1371,1372],{},"Type de câble",[49,1374,1375],{},"Classe CPR",[49,1377,68],{},[49,1379,81],{},[49,1381,94],{},[49,1383,1384],{},"Hors zones",[59,1386,1387,1405,1422,1439,1458],{},[46,1388,1389,1393,1395,1398,1401,1403],{},[64,1390,1391],{},[20,1392,153],{},[64,1394,156],{},[64,1396,1397],{},"Non",[64,1399,1400],{},"Oui",[64,1402,1400],{},[64,1404,1400],{},[46,1406,1407,1411,1413,1415,1418,1420],{},[64,1408,1409],{},[20,1410,173],{},[64,1412,156],{},[64,1414,1397],{},[64,1416,1417],{},"Oui (éclairage)",[64,1419,1400],{},[64,1421,1400],{},[46,1423,1424,1429,1431,1433,1435,1437],{},[64,1425,1426],{},[20,1427,1428],{},"VOB en Preflex gris",[64,1430,194],{},[64,1432,1397],{},[64,1434,1400],{},[64,1436,1400],{},[64,1438,1400],{},[46,1440,1441,1446,1448,1450,1453,1456],{},[64,1442,1443],{},[20,1444,1445],{},"VOB en Preflex vert",[64,1447,194],{},[64,1449,1397],{},[64,1451,1452],{},"Non (cloison creuse)",[64,1454,1455],{},"Restreint",[64,1457,1400],{},[46,1459,1460,1465,1467,1469,1471,1473],{},[64,1461,1462],{},[20,1463,1464],{},"H07Z1-U (sans halogène)",[64,1466,156],{},[64,1468,1397],{},[64,1470,1400],{},[64,1472,1400],{},[64,1474,1400],{},[240,1476,1478],{"id":1477},"notes-importantes-sur-les-types-de-câbles","Notes importantes sur les types de câbles",[245,1480,1481,1486,1496,1502],{},[248,1482,1483,1485],{},[20,1484,252],{}," (câble sous gaine) : Toujours le choix sûr. Adapté pour l'encastrement, le montage en saillie et les chemins de câbles.",[248,1487,1488,1491,1492,1495],{},[20,1489,1490],{},"Preflex gris"," (conduit standard avec VOB pré-tiré) : Autorisé dans les murs massifs. ",[20,1493,1494],{},"Interdit"," dans les cloisons creuses et faux plafonds.",[248,1497,1498,1501],{},[20,1499,1500],{},"Preflex Safe (vert)"," : Dans les murs massifs, le Preflex Safe (Cca) est autorisé même en zone 1. La restriction concerne les cloisons creuses (droogbouw), pas la zone elle-même.",[248,1503,1504,1506],{},[20,1505,274],{}," : Fil sans halogène, particulièrement recommandé pour les zones sensibles. Note : le H07Z1-U en tant que fil individuel n'a pas de classe CPR Cca inhérente — la classe se réfère au système de câblage (fil + conduit). Le H07Z1-U en Preflex Safe atteint Cca.",[11,1508,1510],{"id":1509},"tableau-des-sections","Tableau des sections",[40,1512,1513,1526],{},[43,1514,1515],{},[46,1516,1517,1520,1523],{},[49,1518,1519],{},"Utilisation",[49,1521,1522],{},"Section min.",[49,1524,1525],{},"Disjoncteur",[59,1527,1528,1538,1548,1558,1567],{},[46,1529,1530,1533,1535],{},[64,1531,1532],{},"Éclairage",[64,1534,304],{},[64,1536,1537],{},"10A ou 16A",[46,1539,1540,1543,1545],{},[64,1541,1542],{},"Prises",[64,1544,315],{},[64,1546,1547],{},"16A ou 20A",[46,1549,1550,1553,1555],{},[64,1551,1552],{},"Lave-linge \u002F sèche-linge",[64,1554,315],{},[64,1556,1557],{},"16A (circuit dédié)",[46,1559,1560,1563,1565],{},[64,1561,1562],{},"Chauffe-eau électrique (sous évier, ≤ 2 kW)",[64,1564,315],{},[64,1566,338],{},[46,1568,1569,1572,1575],{},[64,1570,1571],{},"Chauffe-eau instantané (18–27 kW)",[64,1573,1574],{},"6 mm² (32A) ou 10 mm² (40A, triphasé)",[64,1576,1577],{},"32A ou 40A",[11,1579,1581],{"id":1580},"la-protection-différentielle-30ma-est-obligatoire","La protection différentielle 30mA est obligatoire",[16,1583,1584,1585,1588],{},"Selon l'article 7.1.4.3 du RGIE, ",[20,1586,1587],{},"tous les circuits de la salle de bain"," doivent être protégés par un différentiel 30mA — sans exception. Cela s'applique aussi bien à l'éclairage qu'aux prises et aux appareils fixes.",[105,1590,1591],{},[16,1592,1593,1596,1597,1600],{},[20,1594,1595],{},"Attention"," : Même les circuits qui ne font que ",[370,1598,1599],{},"traverser"," la salle de bain (par exemple, des câbles vers les combles) doivent respecter les exigences des zones s'ils passent à l'intérieur des zones de protection.",[11,1602,1604],{"id":1603},"liaison-équipotentielle-dans-la-salle-de-bain","Liaison équipotentielle dans la salle de bain",[16,1606,1607],{},"Important : le RGIE (art. 7.1.4.4) exige une liaison équipotentielle supplémentaire dans la salle de bain — toutes les parties métalliques (conduites d'eau, radiateurs, baignoire, tuyaux d'évacuation) doivent être reliées entre elles et à la borne de terre principale par un conducteur de protection. L'absence de liaison équipotentielle est un motif fréquent de non-conformité lors du contrôle.",[11,1609,1611],{"id":1610},"articles-connexes","Articles connexes",[245,1613,1614,1620],{},[248,1615,1616],{},[390,1617,1619],{"href":1618},"\u002Ffr\u002Fblog\u002F30ma-ddr-par-prise","Ai-je besoin d'un différentiel 30mA par prise ?",[248,1621,1622],{},[390,1623,1625],{"href":1624},"\u002Ffr\u002Fblog\u002Fcontrole-electrique","Contrôle électrique en Belgique — ce qu'il faut savoir",[16,1627,1628],{},[390,1629,1630],{"href":404},"Planifiez l'électricité de votre salle de bain avec PlanElec — gratuit →",{"title":407,"searchDepth":408,"depth":408,"links":1632},[1633,1634,1635,1638,1639,1640,1641],{"id":1266,"depth":408,"text":1267},{"id":1281,"depth":408,"text":1282},{"id":1362,"depth":408,"text":1363,"children":1636},[1637],{"id":1477,"depth":415,"text":1478},{"id":1509,"depth":408,"text":1510},{"id":1580,"depth":408,"text":1581},{"id":1603,"depth":408,"text":1604},{"id":1610,"depth":408,"text":1611},"Le XVB est toujours autorisé, le VOB en conduit seulement sous conditions. Découvrez quels types de câbles sont autorisés dans chaque zone RGIE.","fr",{},"\u002Fblog\u002Fbathroom-cables-arei-zones.fr",{"title":1261,"description":1642},"cables-salle-de-bain-rgie","blog\u002Fbathroom-cables-arei-zones.fr",[434,435,1650,437,252,438,439,1651,1652,442,1653,1654,1655,1256,446,1656,448],"salle de bain","câbles","différentiel","contrôle électrique","installation électrique","Belgique","plan de situation","L_MvtfaVoDtgPwSfXbPjyHTffaIarkqdwoW60DjH-8E",{"id":4,"title":5,"articleId":6,"body":1659,"category":420,"date":421,"description":422,"extension":423,"lastUpdated":421,"locale":424,"meta":1956,"navigation":426,"path":427,"publishDate":421,"readTime":428,"refreshInterval":429,"seo":1957,"slug":431,"stem":432,"tags":1958,"__hash__":449},{"type":8,"value":1660,"toc":1945},[1661,1663,1669,1671,1675,1721,1729,1731,1733,1833,1835,1855,1857,1911,1913,1917,1925,1927,1929,1931,1941],[11,1662,14],{"id":13},[16,1664,18,1665,23,1667,27],{},[20,1666,22],{},[20,1668,26],{},[11,1670,31],{"id":30},[16,1672,34,1673,38],{},[20,1674,37],{},[40,1676,1677,1687],{},[43,1678,1679],{},[46,1680,1681,1683,1685],{},[49,1682,51],{},[49,1684,54],{},[49,1686,57],{},[59,1688,1689,1699,1709],{},[46,1690,1691,1695,1697],{},[64,1692,1693],{},[20,1694,68],{},[64,1696,71],{},[64,1698,74],{},[46,1700,1701,1705,1707],{},[64,1702,1703],{},[20,1704,81],{},[64,1706,84],{},[64,1708,87],{},[46,1710,1711,1715,1719],{},[64,1712,1713],{},[20,1714,94],{},[64,1716,97,1717],{},[20,1718,100],{},[64,1720,103],{},[105,1722,1723],{},[16,1724,1725,112,1727,116],{},[20,1726,111],{},[20,1728,115],{},[16,1730,119],{},[11,1732,123],{"id":122},[40,1734,1735,1751],{},[43,1736,1737],{},[46,1738,1739,1741,1743,1745,1747,1749],{},[49,1740,132],{},[49,1742,135],{},[49,1744,68],{},[49,1746,81],{},[49,1748,94],{},[49,1750,144],{},[59,1752,1753,1769,1785,1801,1817],{},[46,1754,1755,1759,1761,1763,1765,1767],{},[64,1756,1757],{},[20,1758,153],{},[64,1760,156],{},[64,1762,159],{},[64,1764,162],{},[64,1766,162],{},[64,1768,162],{},[46,1770,1771,1775,1777,1779,1781,1783],{},[64,1772,1773],{},[20,1774,173],{},[64,1776,156],{},[64,1778,159],{},[64,1780,180],{},[64,1782,162],{},[64,1784,162],{},[46,1786,1787,1791,1793,1795,1797,1799],{},[64,1788,1789],{},[20,1790,191],{},[64,1792,194],{},[64,1794,159],{},[64,1796,162],{},[64,1798,162],{},[64,1800,162],{},[46,1802,1803,1807,1809,1811,1813,1815],{},[64,1804,1805],{},[20,1806,209],{},[64,1808,194],{},[64,1810,159],{},[64,1812,216],{},[64,1814,219],{},[64,1816,162],{},[46,1818,1819,1823,1825,1827,1829,1831],{},[64,1820,1821],{},[20,1822,228],{},[64,1824,156],{},[64,1826,159],{},[64,1828,162],{},[64,1830,162],{},[64,1832,162],{},[240,1834,243],{"id":242},[245,1836,1837,1841,1847,1851],{},[248,1838,1839,253],{},[20,1840,252],{},[248,1842,1843,259,1845,263],{},[20,1844,258],{},[20,1846,262],{},[248,1848,1849,269],{},[20,1850,268],{},[248,1852,1853,275],{},[20,1854,274],{},[11,1856,279],{"id":278},[40,1858,1859,1869],{},[43,1860,1861],{},[46,1862,1863,1865,1867],{},[49,1864,288],{},[49,1866,291],{},[49,1868,294],{},[59,1870,1871,1879,1887,1895,1903],{},[46,1872,1873,1875,1877],{},[64,1874,301],{},[64,1876,304],{},[64,1878,307],{},[46,1880,1881,1883,1885],{},[64,1882,312],{},[64,1884,315],{},[64,1886,318],{},[46,1888,1889,1891,1893],{},[64,1890,323],{},[64,1892,315],{},[64,1894,328],{},[46,1896,1897,1899,1901],{},[64,1898,333],{},[64,1900,315],{},[64,1902,338],{},[46,1904,1905,1907,1909],{},[64,1906,343],{},[64,1908,346],{},[64,1910,349],{},[11,1912,353],{"id":352},[16,1914,356,1915,360],{},[20,1916,359],{},[105,1918,1919],{},[16,1920,1921,368,1923,373],{},[20,1922,367],{},[370,1924,372],{},[11,1926,377],{"id":376},[16,1928,380],{},[11,1930,384],{"id":383},[245,1932,1933,1937],{},[248,1934,1935],{},[390,1936,393],{"href":392},[248,1938,1939],{},[390,1940,399],{"href":398},[16,1942,1943],{},[390,1944,405],{"href":404},{"title":407,"searchDepth":408,"depth":408,"links":1946},[1947,1948,1949,1952,1953,1954,1955],{"id":13,"depth":408,"text":14},{"id":30,"depth":408,"text":31},{"id":122,"depth":408,"text":123,"children":1950},[1951],{"id":242,"depth":415,"text":243},{"id":278,"depth":408,"text":279},{"id":352,"depth":408,"text":353},{"id":376,"depth":408,"text":377},{"id":383,"depth":408,"text":384},{},{"title":5,"description":422},[434,435,436,437,252,438,439,440,441,442,443,444,445,446,447,448],1775151660093]